| Fire
Hose |
 |
 |
BRISTOL fire
hoses designed for more stringent demands. The hose jacket is again
made of a circular woven high tenacity polyester yarn, which if required,
can also be offered as canvas Fire Hose. For the inner lining a rubber
sleeve is used, providing great flexibility and adhesion for single
or double jackets. This hose is offered in red colour polynothanic
coating in the outside. On request the quality can be further enhanced
providing an increase bursting pressure (upto 150 bar) electro-conductivity
with an electrical resistance below 10 Ohm and or an inner lining
largely resistant against chemicals, oil and petrol.
BRISTOL Fire hoses
for professional, fire brigades, oil field and heavy industry use.
It's
main distinct features is it's all one construction
of synthetic rubber with textile reinforcement meeting B.S 6391 type
and 15636.88 type.
Standard roll length 100ft. or 75ft. other lengths to customer requiorement
can be supplied. |
Features
Highly Protected: The compound of the cover and its profile protects the hose from damage by abrasion, puncture or impact.
Chemical Resistance: Bristol Fire Hose is manufactured to resist contact with a wide range of chemical products: oil, hydrocarbons, alkalis, salt water etc.
Weather Resistance: Outstanding performance at extreme temperature(-20O C + 50O C) protected against atmospheric weathering.
Strong: High Longitudinal tensile strength stands the passage of heavy vehicles. Very resistant to cuts and punctures. Resists continual flexing throughout its service life conserving its original built in strength.
Easily Cleaned: A quick wipe down is sufficient to keep await dirt an grit. If necessary it can be jet washed with detergent to remove chemicals etc.
No Drying: No need to dry the hose. Bristol Fire Hose is mildew, rotproof and waterproof. Water absorption is negligible. Just clean and coil and the hose is ready for service again. |
Technical
Data
| Internal
Diameter |
1" |
1
1/2" |
1
3/4" |
2" |
2
1/2" |
2
3/4" |
3" |
3
1/2" |
4" |
Single
Jacket
Working
Pressure (bar) |
23 |
22 |
20 |
20 |
20 |
20 |
20 |
12 |
12 |
| Bursting
Pressure for 1m (bar) |
70 |
65 |
50 |
50 |
50 |
50 |
50 |
35 |
35 |
| Weight
(5%) (lbs/100ft.) |
9.4 |
15.4 |
16.8 |
20.1 |
25.5 |
29.5 |
32.2 |
38.9 |
48.3 |
Double
Jacket
Working Pressure (bar) |
35 |
25 |
25 |
25 |
25 |
25 |
25 |
20 |
20 |
| Bursting
Pressure for 1m (bar) |
70 |
100 |
80 |
80 |
80 |
80 |
80 |
60 |
60 |
| Weight
(5%) (lbs/100ft.) |
9.4 |
24.8 |
24.8 |
30.2 |
44.3 |
44.3 |
48.2 |
58.4 |
70.5 |
|
|
 |
 |
 |
 |
 |
|
|
 |
 |
|
|
© 2004
BRISTOL Fire Engineering |
 |
| |